84 Publication 2711C-UM001I-EN-P - July 2014
Chapter 6 Troubleshoot the System
Communication 27 Remote Device /*S:0 Param1*/ is Not
Responding
Verify all network connections are correct.
Verify that the communication network cable is
connected.
If new ladder logic is downloading to the controller,
you could see this message. After the download,
communication should run normally.
Verify that the network address of the controller
matches the terminal controller address configured
in the Communication tab.
In the Communication tab, verify that the protocol
specifications are correct, such as communication
rate, data bits, stop bits. These are all protocol
specific.
Communication 28 Invalid Data Address /*S:0 Param1*/ This is not syntactically a valid address.
Communication 30 Bad address in block /*S:0 Param1*/ to /*S:0
Param2*/ on device /*S:0 Param3*/
This can occur when a write only address for a
controller has been set for read/write in the external
tag of the terminal. Param1 to Param2 specifies the
address block having the issue. Somewhere within
the range is where the write only address is defined
in a PanelView external tag. Set the external tag to
write.
Recipe 1001 Recipe upload started. This message is for informational purposes. No
corrective action needed.
Recipe 1002 Recipe save failed. Cause: Recipe in Table has not
been modified.
Make sure that the recipe table is modified before
the save operation is done.
Recipe 1003 Recipe save had errors. This message is for informational purposes. No
corrective action needed.
Recipe 1004 Recipe save completed successfully. This message is for informational purposes. No
corrective action needed.
Recipe 1005 Recipe download failed. Cause: Operation
cancelled.
This message is for informational purposes. No
corrective action needed.
Recipe 1006 Recipe download started. This message is for informational purposes. No
corrective action needed.
Recipe 1007 Recipe download completed with errors. This message is for informational purposes. No
corrective action needed.
Recipe 1008 Recipe download completed successfully. This message is for informational purposes. No
corrective action needed.
PanelView Component Terminal Alerts
Category ID Description Corrective Action

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PanelView 2711C-F2M and is the answer not in the manual?

Allen-Bradley PanelView 2711C-F2M Specifications

General IconGeneral
BrandAllen-Bradley
ModelPanelView 2711C-F2M
CategoryTouch terminals
LanguageEnglish

Related product manuals