- 28 -
MULTIPLE EXPANSIONS
Several Battery Boxes can be connected in a cascade to ensure prolonged autonomy. The connections should be made as shown
here below:
WARNING (only for single UPS): No more than one UPS may be connected to each Battery Box or to more than one
Battery Box connected in a cascade.
SETTING THE RATED BATTERY CAPACITY SOFTWARE CONFIGURATION
Having installed one or more BATTERY BOXES, the TRIPOWER X31 HE must be set up to update the rated capacity value (total
Ah of batteries inside the UPS + external batteries).
This setting should be made using the advanced configuration software UPSTools, present on the CD-ROM provided with the
TRIPOWER X31 HE or directly from the control panel of the UPS.
Installing and running UPSTools:
Follow the installation and operating instructions given in the software manual present in the UPSTools folder of the CD-
ROM.
Making the setting from the display
Set the rated battery capacity following the indications given in the “USE” chapter.