POWERING ON FROM THE MAINS
Power the TRIPOWER X31 HE by closing the SWIN input switch and leaving the SWMB maintenance switch open; if present,
set the “1/0” switch to “1”.
After a few moments, the TRIPOWER X31 HE is turned on, the capacitors are precharged and the "Lock / stand-by" LED
blinks: The UPS is in stand-by mode.
Press the button to access the power-on menu. When prompted to confirm, select “YES” and press the button again.
All the LEDs around the display light up for about 1 sec. and a beep is emitted. The message “START UP” appears on the
display to inform the user of the beginning of the start up sequence which ends with transition of the TRIPOWER X31 HE to
load powered by the inverter.
POWERING ON FROM THE BATTERY
If present, set the “1/0” switch to “1”.
Hold the “Cold Start” key down for about 5 seconds. The TRIPOWER X31 HE will start and the display will light up.
Press the button to gain access to the power-on menu. When prompted to confirm, select “YES” and press the again.
All the LEDs around the display light up for about 1 sec. and the buzzer starts to beep once about every 7 seconds.
Note: if the sequence described above is not executed within 1 min., the UPS turns itself off to avoid discharging the batteries
unnecessarily.
POWERING OFF THE TRIPOWER X31 HE
From the main menu, select the “SYSTEM STBY” item and press to gain access to the submenu and press it again to confirm
the operation. To shut down the TRIPOWER X31 HE completely, set the “1/0” switch (if present) to “0” and open the SWIN input
switch.
Note: during prolonged periods of inactivity, it is good practice to shut down the TRIPOWER X31 HE using the
“1/0” switch (if present); open the input and output switches and lastly, with the UPS off, open the battery fuse
holders.