- 38 -
CONFIGURING THE TRIPOWER X31 HE
The table below illustrates all the possible settings at your disposal to tailor the TRIPOWER X31 HE to best satisfy your needs.
CP (Control Panel) = Indicates that the configuration can be changed not only from the configuration software but also from
the control panel.
SW (Software) = Indicates that the configuration may only be changed from the configuration software.
FUNCTION DESCRIPTION DEFAULT POSSIBLE SETTINGS MOD.
Output frequency
Selects rated
output frequency
50 Hz
50 Hz
60 Hz
CP
Output voltage
Selects rated
output voltage
(Phase / Neutral)
230V
200V *
208V *
220V
230V
240V
220 ÷ 240 in steps of 1V
(via software only)
CP
Operating mode
Selects one of the
5 operating modes
ON LINE
ON LINE
ECO
SMART ACTIVE
STAND-BY OFF
FREQUENCY CONVERTER
(via software only)
CP
Power off due to
minimum load
Automatically powers off
UPS in battery operation,
if the load is less than 5%
Disabled
Enabled
Disabled
CP
Autonomy limitation
Sets the maximum time
of operation on battery
power
Disabled
Disabled (complete battery
discharge)
1 ÷ 65000 in steps of 1 sec.
SW
Battery low
prealarm
Sets the estimated
autonomy time left for
battery low warning
3 min. 1 ÷ 255 in steps of 1 min.
SW
Battery test
Sets the time interval for
automatic battery test
40 hours
Disabled
1 ÷ 1000 in steps of 1 hour
SW
Maximum load
alarm threshold
Selects the user
overload limit
Disabled
Disabled
0 ÷ 103 in steps of 1%
SW
Sound alarm
Selects the operating
mode of the sound alarm
Reduced
Normal
Reduced:
does not sound when
bypass is activated
momentarily
CP
Auxiliary socket
(power share)
Selects the operating
mode of the auxiliary
socket
Always
connected
Always connected
Disconnected after n seconds of
battery operation
Disconnected n seconds after the
end of discharge alarm signal
... (see manual of UPSTools)
SW
Battery expansion
Sets the Ah installed
(external battery
extension)
0 Ah
Min.: 0 - Max.: 999
(in steps of 1 unit)
CP
Language
Selects the display
language
English
English
Italian
German
.......
CP
Date and Time
Set the date and time -- --
CP