- 51 -
Lock: indicate a breakdown of the TRIPOWER X31 HE or one of its parts. Locks are normally preceded by an alarm
signal. In the event of a fault and resultant breakdown of the inverter, the inverter will be switched off and the load will be
powered by the bypass line (this procedure is excluded for breakdowns caused by high and persistent overloads and by
short circuits).
CODE DESCRIPTION
L01
Incorrect auxiliary power supply
L02
One or more internal cables disconnected
L03
Phase 1 input fuse broken or input relay locked (will not close)
L04
Phase 2 input fuse broken or input relay locked (will not close)
L05
Phase 3 input fuse broken or input relay locked (will not close)
L06
BOOST stage overvoltage positive
L07
BOOST stage overvoltage negative
L08
BOOST stage undervoltage positive
L09
BOOST stage undervoltage negative
L10
Static bypass switch fault
L11
Bypass output breakdown
L14
Inverter overvoltage
L17
Inverter undervoltage
L20
Direct voltage at output of inverter or Sine wave inverter distorted
L23
Overload at output
L26
Short circuit at output of Phase1
L29
output fuse broken or output relay locked (will not close)
L34
Heat sink 1 overtemperature
L35
Heat sink 2 overtemperature
L36
Heat sink 3 overtemperature
L37
Battery charger overtermperature
L38
Temperature probe of heat sink 1 faulty
L39
Temperature probe of heat sink 2 faulty
L40
Temperature probe of heat sink 3 faulty
L41
Temperature probe of battery charger faulty
L42
BOOST battery 1 fuse blown
L43
BOOST battery 2 fuse blown
L44
BOOST battery 3 fuse blown