EasyManua.ls Logo

Alpha Technologies Tri Power X31 HE - Page 53

Alpha Technologies Tri Power X31 HE
55 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 53 -
TRIPOWER X31 HE Models 10 kVA 15 kVA 20 kVA
Dimensions and weight
W x D x H
Optional Small Size 320 x 840 x 930 mm
Standard 440 x 850 x 1320 mm
Weight without batteries
Optional Small Size 80 Kg 90 Kg 95 Kg
Standard 105 Kg 115 Kg 120 Kg
Weight with batteries
Optional Small Size 180 Kg 190 Kg 195 Kg
Standard 305 Kg 315 Kg 320 Kg
Modes and efficiency values
Operating modes
True on line double conversion
ECO mode
Smart Active mode
Stand-by Off (Emergency)
Frequency Converter
AC/AC efficiency in on line mode
93.5% 94%
AC/AC efficiency in Eco mode
98%
DC/AC efficiency in autonomy mode ≥92.5% ≥93.5%
Miscellaneous
Noise ≤48dB(A) ≤52dB(A)
Color RAL 7016
Ambient temperature
(6)
0 – 40 °C
(1)
To maintain the output voltage within the range of precision indicated, it may have to be recalibrated after a long period of operation
(2)
If the mains frequency is within ± 5% of the selected value, the TRIPOWER X31 HE is synchronized with the mains. If the frequency is outside
the tolerance limits or running on the battery, the frequency is the value selected +0.1%
(3)
Mains/Battery @ load 0% -100%
(4)
@ Mains / battery / mains @ resistive load 0% / 100% / 0%
(5)
The recharging current is regulated automatically according to the capacity of the battery installed
(6)
20 – 25 °C for maximum battery life
(7)
@ 100% load & THDv ≤ 1%