Technical Guide P12y/EN FT/D22
User Guide
MiCOM P125/P126/P127 Page 101/108
4.6.11.3 Submenu AND Logic Equat. T Delay
AUTOMAT. CTRL
Heading of AUTOMAT. CTRL menu.
To gain access to the AND logic equat submenu, press
2 and 6 until the submenu is reached.
AND logic equat
T delay
Heading of submenu.
To navigate within submenu points, press 8 2. To
modify setting, press 5. Use 8 2 4 6 to scroll and set
available selections. Press 5 to confirm choice.
EQU. A Toperat
600.00 s
Displays setting value of operating delay time (Toperat)
for logic equation A .
Setting range is from 0 to 600s, in steps of 10ms.
EQU. A Treset
600.00 s
Displays setting value of reset delay time (Treset) for
logic equation A.
Setting range is from 0 to 600s, in steps of 10ms.
EQU. B Toperat
600.00 s
Displays setting value of operating delay time (Toperat)
for logic equation B.
Setting range is from 0 to 600s, in steps of 10ms.
EQU. B Treset
600.00 s
Displays setting value of reset delay time (Treset) for
logic equation B.
Setting range is from 0 to 600s, in steps of 10ms.
EQU. C Toperat
600.00 s
Displays setting value of operating delay time (Toperat)
for logic equation C.
Setting range is from 0 to 600s, in steps of 10ms.
EQU. C Treset
600.00 s
Displays setting value of reset delay time (Treset) for
logic equation C.
Setting range: from 0 to 600s, in steps of 10ms.
EQU. D Toperat
600.00 s
Displays setting value of operating delay time (Toperat)
for logic equation D.
Setting range: from 0 to 600s, in steps of 10ms.
EQU. D Treset
600.00 s
Displays setting value of reset delay time (Treset) for
logic equation D.
Setting range: from 0 to 600s, in steps of 10ms.