4.2.7 Submenu Output Relay 1 in Fail Safe mode
CONFIGURATION
Heading of CONFIGURATION menu.
To gain access to the Inputs submenu, press 2, 6 until
the submenu is reached.
RL1 Output relay
Heading of the RL1 Output relay submenu.
To gain access to the submenu content, press 2.
Fail Safe Relay
Yes
Fail safe Relay = No means that the RL1 output relay is
normally de-energized and picks-up in case of trip
(standard configuration).
Fail-safe Relay = Yes means that the RL1 output relay
is normally energized and drops in case of trip (or in
case of fail of auxiliary voltage, or coil interruption,
etc.). To modify press 5 and using 8 2 keys Press 5
to confirm the setting.
4.2.8 Submenu Selecting Active Protection Group (P125, P126 & P127)
CONFIGURATION
Heading of CONFIGURATION menu.
To gain access to the Group Select menu, press 2 and
6 until the submenu is reached.
Group Select
Heading Group Select submenu.
To gain access to the submenu content press 2.
Change Group
By Input LEVEL
To select the way to active the setting group 1or 2 press
5 and 8 2 to choose on the LEVEL or on the EDGE.
Press 5 to confirm your choice.
Setting Group
1
To select active setting protection group 1 or 2 press 5
and 8 or 2.
Press 5 to confirm choice.