P12y/EN FT/D22 Technical Guide
User Guide
Page 20/108 MiCOM P125/P126/P127
Led 5
tPe/IeCos>> No
Setting choice Yes: LED 5 lights up when tPe>> or
IeCos>> delay time has elapsed.
Setting choice No: No operation when tPe>> or
IeCos>> delay time has elapsed.
Led 5
I> No
Setting choice Yes: LED 5 lights up when I> threshold
is exceeded.
Setting choice No: No operation when I> threshold is
exceeded.
Led 5
tI> No
Setting choice Yes: LED 5 lights up when tI> delay time
has elapsed.
Setting choice No: No operation when tI> delay time
has elapsed.
Led 5
I>> No
Setting choice Yes: LED 5 lights up when I>> threshold
is exceeded.
Setting choice No: No operation when I>> threshold
is exceeded.
Led 5
tI>> No
Setting choice Yes: LED 5 lights up when tI>> delay
time has elapsed.
Setting choice No: No operation when tI>> delay time
has elapsed.
Led 5
I>>> No
Setting choice Yes: LED 5 lights up when I>>>
threshold is exceeded.
Setting choice No: No operation when I>>> threshold
is exceeded.
Led 5
tI>>> No
Setting choice Yes: LED 5 lights up when tI>>> delay
time has elapsed.
Setting choice No: No operation when tI>>> delay
time has elapsed.
Led 5
I< No
Setting choice Yes: LED 5 lights up when I< threshold
is exceeded.
Setting choice No: No operation when I< threshold is
exceeded.
Led 5
tI2> No
Setting choice Yes: LED 5 lights up when tI2> delay
time has elapsed.
Setting choice No: No operation when tI2> delay time
has elapsed.
Led 5
Brkn. Cond No
Setting choice Yes: LED 5 lights up when Brkn. Cond is
detected.
Setting choice No: No operation when Brkn. Cond is
detected.
Led 5
Therm Trip No
Setting choice Yes: LED 5 lights up when Thermal Trip
occurs.
Setting choice No: No operation when Thermal Trip
occurs.