Technical Guide P12y/EN FT/D22
User Guide
MiCOM P125/P126/P127 Page 43/108
I>>
Torque 90 °
Displays setting value for the torque angle.
Torque angle setting range is from 0° to 359 °, in steps
of 1°.
I>>
Trip Zone ±10 °
Displays angle value for the Trip Zone.
This defines the operating region to either side of the
torque angle. Setting range is from ±10° to 170°, in
steps of 1°.
t I>>
150.00 s
Displays setting value for the trip threshold.
The setting range is from 0 to 150s, in steps of 10ms.
By pushing 2 the next window will display the threshold menu I>>>.
4.5.1.8 Threshold Menu I>>>
I>>> ?
Yes
Selection of the third alarm threshold function for
phase OC (I>>>). Setting choice: No, Yes, DIR.
If the user selects Yes, the following window is shown:
If the user selects DIR, the directional choice window is
shown.
If the user selects No, next window will show the
submenu [67] Phase OC.
I>>>
10.00 In
Displays setting value for the alarm threshold.
The threshold setting range is from 0.5 to 40 In, in
steps of 0.01 In.
t I>>>
150.00 s
Displays setting value for the trip threshold.
The setting range is from 0 to 150 s, in steps of 10ms.
By pushing 2 the next window will display the [67] Phase OC, the header of the
menu.
I>>> ?
DIR
Selection of the third alarm threshold function for
phase OC (I>>>). Setting choice: No, Yes, DIR.
If the user selects DIR, the following window is shown:
If the user selects Yes, the non-directional choice
window is shown.
If the user selects No, next window will show the
submenu [67] Phase OC.
I>>>
10.00 In
Displays setting value for the alarm threshold.
The threshold setting range is from 0.5 to 40 In, in
steps of 0.01 In.