EasyManua.ls Logo

Alstom MiCOM P125 - Page 64

Alstom MiCOM P125
110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P12y/EN FT/D22 Technical Guide
User Guide
Page 62/108 MiCOM P125/P126/P127
4.5.5.4 Threshold Menu I2> ANSI/IEEE
Delay Type
ANSI/IEEE
Displays the type of ANSI/IEEE curves for I2> delay
time.
TMS
1.00
Displays the TMS factor associated to ANSI/IEEE family
of curves.
The setting range is from 0.025 to 1.5, in steps of
0.025.
4.5.5.5 Reset Threshold Menu I2> DMT/IDMT IEEE/ANSI
Reset Delay Type
DMT
Displays the reset delay time type for ANSI/IEEE definite
delay time curves.
tReset
0.00 s
Displays setting value for the reset time.
The setting range is from 0 to 100 s, in steps of 10 ms.
By pushing 2 the next window will display the I2>>?
Reset Delay Type
IDMT
Displays the selected reset delay type for ANSI/IEEE
inverse delay time curves.
RTMS
1.000
Displays the RTMS factor associated to IDMT delay type
reset.
The setting range is from 0.025 to 1.5, in steps of
0 025
By pushing 2 the next window will display the I2>>?
4.5.5.6 Threshold Menu I2>>
I2>> ?
Yes
Selection of the second alarm threshold function for
Negative Phase Sequence OC (I2>>). Setting choice:
No, Yes
If the user selects Yes, the following window is shown:
If the user selects No, the next window will show the
threshold menu I2>>>.
I2>> =
5.00 In
Displays setting value for the alarm threshold.
The threshold setting range is from 0.5 to 40 In, in
steps of 0.01 In.
t I2>>
150.00 s
Displays setting value for the trip threshold.
The setting range is from 0 to 150 s, in steps of 10ms.
By pushing 2 the next window will display the I2>>>?

Table of Contents