P12y/EN FT/D22 Technical Guide
User Guide
Page 84/108 MiCOM P125/P126/P127
tIe>> :8765432
1100010
Assigning second trip threshold for earth fault
overcurrent (tIe>>) to the output relays; i.e. to output
3, 7 & 8 (RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Ie_R>> :8765432
0000010
Assigning second trip threshold for directional earth
fault overcurrent from the inverse trip zone (Ie_R>>) to
the output relays; i.e. to output 3 (RL3).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Ie>>> :8765432
1100010
Assigning third alarm threshold for earth fault
overcurrent (Ie>>>) to the output relays; i.e. to output
3, 7 & 8 (RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
tIe>>> :8765432
1000010
Assigning third trip threshold for earth fault overcurrent
(tIe>>>) to the output relays; i.e. to output 3 & 8 (RL3
& RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Ie_R>>> :8765432
1100010
Assigning third trip threshold for directional earth fault
overcurrent from the inverse trip zone (Ie_R>>>) to
the output relays; i.e. to output 3, 7 & 8 (RL3, RL7 &
RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Pe/ :8765432
IeCos> 1100010
Assigning first earth wattmetric alarm threshold
(Pe/IeCos>) to the output relays; i.e. to output 3, 7 & 8
(RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
tPe/ :8765432
IeCos> 0000010
Assigning first earth wattmetric trip threshold
(tPe/IeCos>) to the output relays; i.e. to output 3 (RL3).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Pe/ :8765432
IeCos>> 1100010
Assigning second earth wattmetric alarm threshold
(Pe/IeCos>>) to the output relays; i.e. to output 3, 7 &
8 (RL3, RL7 & RL8).
Setting choice: 1 assigning to the output relay; 0 no
assignment.
tPe/ :8765432
IeCos>> 1100010
Assigning second earth wattmetric trip threshold
(tPe/IeCos>>) to the output relays; i.e. to output 3, 7
& 8 (RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.