Technical Guide P12y/EN FT/D22
User Guide
MiCOM P125/P126/P127 Page 97/108
Ie>> :DCBA
0000
Assigning second alarm threshold for earth fault
overcurrent (Ie>>) to one (or more) of the logic
equations A, B, C and D.
Setting choice: 1 assigns the logic equation; 0 no
assignment.
t Ie>> :DCBA
0000
Assigning second trip threshold for earth fault
overcurrent (tIe>>) to one (or more) of the logic
equations A, B, C and D.
Setting choice: 1 assigns the logic equation; 0 no
assignment.
Ie>>> :DCBA
0000
Assigning third alarm threshold for earth fault
overcurrent (Ie>>>) to one (or more) of the logic
equations A, B, C and D.
Setting choice: 1 assigns the logic equation; 0 no
assignment.
t Ie>>> :DCBA
0000
Assigning third trip threshold for earth fault overcurrent
(tIe>>>) to one (or more) of the logic equations A, B,
C and D.
Setting choice: 1 assigns the logic equation; 0 no
assignment.
Pe :DCBA
IeCos> 0000
Assigning first earth wattmetric alarm threshold
(Pe/IeCos>) to one (or more) of the logic equations A,
B, C and D.
Setting choice: 1 assigns the logic equation; 0 no
assignment.
tPe/ :DCBA
IeCos> 0000
Assigning first earth wattmetric trip threshold
(tPe/IeCos>) to one (or more) of the equations A, B, C
and D.
Setting choice: 1 assigns the logic equation; 0 no
assignment.
Pe/ :DCBA
IeCos>> 0000
Assigning second earth wattmetric alarm threshold
(Pe/IeCos>>) to one (or more) of the equations A, B,
C and D.
Setting choice: 1 assigns the logic equation; 0 no
assignment.
tPe/ :DCBA
IeCos>> 0000
Assigning second earth wattmetric trip threshold
(tPe/IeCos>>) to one (or more) of the equations A, B,
C and D.
Setting choice: 1 assigns the logic equation; 0 no
assignment.
I2> :DCBA
0000
Assigning first alarm threshold for negative sequence
overcurrent (I2>) to one (or more) of the equations A,
B, C and D.
Setting choice: 1 assigns the logic equation; 0 no
assignment.