Technical Guide P12y/EN FT/D22
User Guide
MiCOM P125/P126/P127 Page 57/108
Delay Type
DMT
Displays threshold delay time type. Setting choices are:
DMT (definite time) RI for the electromechanical inverse
time curve, IEC-XX, CO2, CO8, IEEE-XX inverse time
delay curve and RECT curve.
If the user selects DMT the following menu is displayed:
t Pe>
150.00 s
Displays setting value for the trip threshold.
The setting range is from 0 to 150s, in steps of 10ms.
tReset
0.10 s
Displays setting value for the reset time.
The setting range is from 0 to 100 s, in steps of 10ms.
By pushing 2 the next window will display the Pe>>?
4.5.4.1 Threshold Menu Pe/IeCos> RI
Delay Type
RI
Displays threshold delay time type. Setting choices are:
DMT (definite time) RI for the electromechanical inverse
time curve, IEC-XX, CO2, CO8, IEEE-XX inverse time
delay curve and RECT curve.
If the user selects RI the following menu is displayed:
K
1.000
Selection of K value for the RI curve.
The setting range is from 0.100 to 10, in steps of
0.005.
tReset
0.04 s
Displays setting value for the reset time.
The setting range is from 0 to 100 s, in steps of 10ms.
By pushing 2 the next window will display the Pe>>?
4.5.4.2 Threshold Menu Pe/IeCos> IEC-XX
Delay Type
IEC-STI
Displays threshold delay time type. Setting choices are:
DMT (definite time) RI for the electromechanical inverse
time curve, IEC-XX, CO2, CO8, IEEE-XX inverse time
delay curve and RECT curve.
If the user selects IEC curve the following menu is
displayed:
TMS
1.000
Displays TMS value for the curve.
The setting range is from 0.025 to 1.5, in steps of
0.025.
tReset
0.04 s
Displays setting value for the reset time.
The setting range is from 0 to 100 s, in steps of 10ms.
By pushing 2 the next window will display the Pe>>?

Table of Contents