P12y/EN FT/D22 Technical Guide
User Guide
Page 58/108 MiCOM P125/P126/P127
4.5.4.3 Threshold Menu Pe/IeCos> RECT
Delay Type
RECT
Displays threshold delay time type. Setting choices are:
DMT (definite time) RI for the electromechanical inverse
time curve, IEC-XX, RECT, CO2, CO8, IEEE-XX inverse
time delay curve and RECT curve.
If the user selects IEC curve the following menu is
displayed:
TMS
1.000
Displays TMS value for the curve.
The setting range is from 0.025 to 1.5, in steps of
0.025.
tReset
0.04 s
Displays setting value for the reset time.
The setting range is from 0 to 100 s, in steps of 10ms.
By pushing 2 the next window will display the Pe>>?
4.5.4.4 Threshold Menu Pe/IeCos> ANSI/IEEE
Delay Type
IEEE-EI
Displays threshold delay time type. Setting choices are:
DMT (definite time) RI for the electromechanical inverse
time curve, IEC-XX, CO2, CO8, IEEE-XX inverse time
delay curve and RECT curve.
If the user selects IEEE/ANSI curve, the following menu
is displayed:
TMS
1.000
Displays TMS value for the curve.
The setting range is from 0.025 to 1.5, in steps of
0.025.
4.5.4.5 Reset Threshold Menu Pe/IeCos> DMT/IDMT IEEE/ANSI
Reset Delay Type
DMT
Displays the reset delay time type.
Select between DMT (Definitive Time) and IDMT
(Inverse Time).
If the user selects DMT delay type, the following menu
is displayed:
tReset
1.00 s
Displays setting value for the reset time.
The setting range is from 0 to 100 s, in steps of 10ms.
By pushing 2 the next window will display the Pe>>?