Technical Guide P12y/EN FT/D22
User Guide
MiCOM P125/P126/P127 Page 87/108
79 Run :8765432
1100010
Assigning the "autoreclose in progress" information to
the output relays; i.e. to output 3, 7 & 8 (RL3, RL7 &
RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
79 Trip :8765432
1100010
Assigning the autoreclose final trip signal to the output
relays; i.e. to output 3, 7 & 8 (RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Active :8765432
Group 0000010
Assigning the active setting group to the output relays;
i.e. to output 3 (RL3).
Setting choice: 1 assigns the output relay; 0 no
assignment.
t EQU.A :8765432
1000000
Assigning the logic AND equation A result trip signal to
the output relays; i.e. to output 8 (RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
t EQU.B :8765432
1000000
Assigning the logic AND equation B result trip signal to
the output relays; i.e. to output 8 (RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
t EQU.C: 8765432
1000000
Assigning the logic AND equation C result trip signal to
the output relays; i.e. to output 8 (RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
t EQU.D: 8765432
1000000
Assigning the logic AND equation D result trip signal to
the output relays; i.e. to output 8 (RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
4.6.5.2.1 Additional Output Relay Menu Points for P127
U> :8765432
0100010
Assigning first alarm threshold for overvoltage (U>) to
the output relays; i.e. to output 3 & 7 (RL3 & RL7).
Setting choice: 1 assigns the output relay; 0 no
assignment.
tU> :8765432
0000010
Assigning first trip threshold for overvoltage (tU>) to
the output relays; i.e. to output 3 (RL3).
Setting choice: 1 assigns the output relay; 0 no
assignment.
U>> :8765432
0100010
Assigning second alarm threshold for overvoltage
(U>>) to output relays; i.e. to output 3 & 7 (RL3 &
RL7).
Setting choice: 1 assigns the output relay; 0 no
assignment.