P12y/EN FT/D22 Technical Guide
User Guide
Page 86/108 MiCOM P125/P126/P127
tI< :8765432
1100010
Assigning trip threshold for undercurrent (tI<) to the
output relays; i.e. to output 3, 7 & 8 (RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Ue>>>> :8765432
1100010
Assigning alarm threshold for residual overvoltage to
the output relays; i.e. to output 3, 7 & 8 (RL3, RL7 &
RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
tUe>>>>: 8765432
1100010
Assigning trip threshold for residual overvoltage to the
output relays; i.e. to output 3, 7 & 8 (RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Brkn :8765432
Cond 1100010
Assigning Broken Conductor alarm signal to the output
relays; i.e. to output 3, 7 & 8 (RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
CB :8765432
Alarm 1100010
Assigning circuit breaker alarm function signal (CB
Open NB, SAmps(n), CB Open Time and CB Close
Time) to the output relays; i.e. to output 3, 7 & 8 (RL3,
RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
52 Fail :8765432
1100010
Assigning circuit breaker trip supervision failure
function signal to the output relays; i.e. to output 3, 7 &
8 (RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
CB :8765432
Fail 0001010
Assigning circuit breaker failure function timer signal
(tBF) to the output relays; i.e. to output 3 & 5 (RL3 &
RL5).
Setting choice: 1 assigns the output relay; 0 no
assignment.
CB :8765432
Close 0100010
Assigning circuit breaker closing order signal to the
output relays; i.e. to output 3 & 7 (RL3 & RL7).
Setting choice: 1 assigns the output relay; 0 no
assignment.
tAux1 :8765432
1100010
Assigning delayed auxiliary input Aux 1 to the output
relays; i.e. to output 3, 7 & 8 (RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
tAau2 :8765432
1100010
Assigning delayed auxiliary input Aux 2 to the output
relays; i.e. to output 3, 7 & 8 (RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.