GROUP 1
Note:
#. If the function is set as enable then the relay will allow editing the settings of respective sub menus. If the
function is set as disable then the relay will not allow editing the settings of sub menus and will bypass the
protection function.
* The User can scroll the previous settings by using the Plus / Up arrow key (+ /
).
** After Editing any sub menus of the Thermal Overload setting If the SET/ Left (
) arrow key is pressed, the
Relay ask SET to SAVE the changes or RESET to CANCEL the changes.
2.3.14.2 Edit settings (if Thermal Overload function is Single)
Thermal Overload
By using the Plus / Up arrow key (+ /) or Minus / Right arrow key (-
/) select the Thermal Overload setting menu in Group 1.
Press the Left arrow key () to move to the next option.
Characteristic
Single
Press the Edit Key, the text will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired Characteristic can set i.e. Single / Disable. #
After selecting the desired Characteristic press the Edit Key, the text will
stop blinking.
Press the Left arrow key () to move to the next option. *
Thermal Trip
1.00 A
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired Thermal Trip can be set. The setting range is from 0.10
to 4.00 in steps of 0.01.
After editing the desired Thermal Trip press the Edit Key, the number will
stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
Thermal Alarm
070
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired Thermal Alarm can be set. The setting range is from
050 to 100 in steps of 1.
After editing the desired Thermal Alarm press the Edit Key, the number
will stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *