I<
1.00 A
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired I< settings can be set. The setting range is from 0.10 to
1.00 in steps of 0.01.
After editing the desired I< setting press the Edit Key, the number will
stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
t I<
001.00
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired t I< setting can be set. The setting range is from 000.20
to 100.00 in steps of 0.01.
After editing the desired t I< setting press the Edit Key, the number will
stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
I<
1.00 A
The window displays the first setting of the under current Protection
menu.
Press the Left arrow key () to move to the next option.
SET For Save
RESET For Cancel
Press the SET / Left arrow key () to SAVE the changes.
Press the RESET key to CANCEL the changes.
OK
When the SET / Left arrow key () is pressed the relay will SAVE the
changes and this window will flash for moment. The control will return to
the Main Menu
GROUP 1
Note:
#. If the function is set as enable then the relay will allow editing the settings of respective sub menus. If the
function is set as disable then the relay will not allow editing the settings.
* The User can scroll the previous settings by using the Plus / Up arrow key (+ /
).
** After Editing any sub menus of the Under Current protection setting, If the SET/ Left (
) arrow key is
pressed, the Relay ask SET to SAVE the changes or RESET to CANCEL the changes.