SS-DPTAC www.amana-ptac.com 5
4 www.amana-ptac.com SS-DPTAC
SPecification SHeet
SPecification SHeet
Voltage
Electric
Heater
Size (kW)
No. of
Stages
Nominal Heating (BTU/h)
Total
Watts6
Total Amps
8
Minimum
Circuit
Ampacity²
MOD
4
(amps)
Power
Cord
@ 230V @ 208V @ 265V
230/208V 2.5/2.0 1 8,500 6,800 - - 2,650/2,140 11.5/10.2 14.2 15 6 - 15 P
230/208V 3.5/2.9 1 12,000 9,900 - - 3,650/3,040 15.8/14.5 19.6 20 6 - 20 P
230/208V 5.0/4.1 1* 17,100 14,000 - - 5,150/4,240 22.3/20.3 27.7 30 6 - 30 P
265V 2.5 1 - - - - 8,500 2,650 10.0 12.4 15 7 - 20 P
265V 3.7 1 - - - - 12,600 3,850 14.6 18.1 20 7 - 20 P
265V 5.0 1* - - - - 17,100 5,150 19.5 24.2 25 7 - 30 P
* PTH/PTC09*B50*G/K has the same airow as a PTC/PTH12*B***G (not available on 7,000 BTU/h models).
Notes:
1– All 265-volt models must use an Amana
®
brand sub-base (PTSB4**E) or an Amana
®
brand hard-wire kit (PTPWHWK4).
2– Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.
3– Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
Minimum voltage on 265-volt models is 238.5 volts; maximum is 291.5 volts.
4– Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style
time-delay fuses (included and factory-installed on all Amana
®
brand 265-volt chassis).
5– Heating capacity and efciency based on unit operation without condensate pump; unit automatically switches to electric heat
at approximately 24°F outdoor ambient.
6– Total watts for 12,000 and 15,000 BTU/h models; subtract 70 watts for PT07/09*B**A*
7– Specify two-digit heater kW size to complete model number.
8– Total amps for 12,000 and 15,000 BTU/h models; subtract 0.2 amps for PT07/09*B*A*.
9– R-22 refrigerant used in all systems.
10– All units meet or exceed ASHRAE 90.1 standards.
11– All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
Ptc and PtH modelS — electric Heat Performance
(Primary Heating for PTC Models; Auxiliary Heating for PTH Models; See below for Power Cord Conguration)
Product SPecificationS (cont.)
All units come with factory-installed power cords.
All units less than 250 volts come with LCDI device.
Power Receptacle Conguration
NEMA6-30R; 250V receptacle,
used on 230/208V units
G
NEMA7-30R; 277V receptacle,
used on 265V units
G
NEMA6-15R; 250V receptacle,
used on 230/208V units
G
NEMA6-20R; 250V receptacle,
used on 230/208V units
G
W
NEMA7-20R; 277V receptacle,
used on 265V units
G
277V Rating Power Cord Plugs
NEMA 7 Conguration
G
W
20 amp
G
W
30 amp
250V Rating Power Cord Plugs with LCDI Device
NEMA 6 Conguration
Power Cord Plugs
15 amp
20 amp
30 amp
PoWer cord configuration
contract Bid SPecificationS
Please visit www.amana-ptac.com to download the contractor bid specications information.