A.3 MOUNTING CLEARANCES
The heater should be positioned so that clearances from
combustible materials will meet or exceed those shown
in the following table. Also, ensure that there is at least
6” clearance on all sides of the burner for service access
and for free flow of combustion air. When the heater is
angle mounted, the burner/control assembly must remain
horizontal.
Ensure that there is adequate provision in the building
for combustion and ventilation supply. Installation must
meet minimum requirements and applicable codes.
A.2 PACKAGING AND SHIPPING
INFORMATION
See appendix “A” for assembly drawings.
Material list with part numbers and descriptions for each
part will accompany each shipment.
Heaters include: Options:
Burner/Control 1 180° Bend
Radiant Tubes 1 or 2 90° Bends
Reflectors Flex Gas Connector
Brackets Ball Valve
Fan Vent Hoods
U-Bend (U-tube only) Hanging Assembly
Tube Couplings (Chain etc)
Shipping packages for individual projects will be boxed
and crated as outlined in the specific bill of lading.
Minimum Clearances to Combustible.
Suggested Mounting Height Above Floor.
(Minimum / Recommended in Feet)
C2
C1
A
B1
BB
A
E
D2
0° to 55°
D1
Ensure that there is adequate provision in the
building for combustion and ventilation air
supply. Installation must meet minimum
requirements and appliciable codes.
Burner end.
Outlet end.
Angled view.
End view.
C3
Below
heater
Side
flued
Side
unvented
End
unvented
Above outlet
unvented
Above
Reflector
Above
Burner
Behind
Burner
Return end on
U tube heater
Model(s) Input A B B1 C1 C2 C3 D1 D2 E
VPLUS40
41,500 49 24 41 20 8 22 8 12 10
VPLUS80
80,000 74 29 41 20 6 22 8 12 10
VPLUS100
100,000 74 32 41 20 6 22 8 16 10
VPLUS125
123,500 74 39 47 20 6 22 20 18 10
VPLUS150
150,000 74 39 48 20 6 22 20 18 10
VPLUS170
169,000 86 48 48 20 6 22 20 20 10
VPLUS200
200,000 86 48 48 20 6 22 20 20 10
VPLUS225
222,500 86 48 48 20 6 22 20 22 10
40 80 100 125 150 170 200 225
Standard
min ft 12 12 14 14 16 16 18 18
rec ft 14 14 16 16 18 18 20 20
min ft 10
10 12 12 14 14 16 16
rec ft
11 11 13 13 15 15 17 17
Inclined
Y
WARNING. FIRE OR EXPLOSION HAZARD - can cause death, severe injury, or property damage. Fail-
ure to maintain specified minimum clearances to combustibles could result in a serious fire hazard. DO NOT
locate flammable or combustible materials within minimum distances specified in the preceding tables.