INSPECTION, MAINTENANCE AND
RECHARGE SERVICE MANUAL
P/N 05603
All fire extinguishers should be installed, inspected and maintained in
accordance with the National Fire Protection Association standard titled
"Portable Fire Extinguishers", NFPA-10 and the requirements of local
authorities having jurisdiction.
When maintenance is indicated, it should be performed by trained
persons having proper equipment. Fire extinguishers are pressure
vessels and must be treated with respect and handled with care. They
are mechanical devices and require periodic maintenance to be sure that
they are ready to operate properly and safely. Amerex strongly
recommends that the maintenance of portable fire extinguishers be done
by a trained professional your local authorized Amerex Distributor.
Amerex Corporation makes original factory parts available to insure
proper maintenance USE OF SUBSTITUTE PARTS RELEASES
AMEREX OF ITS WARRANTY OBLIGATIONS. Amerex parts have
machined surfaces and threads that are manufactured to exacting
tolerances. O-rings, hoses, nozzles, and all metal parts meet precise
specifications and are subjected to multiple in-house inspections and
tests for acceptability. There are substitute parts available that may be
incorrectly labeled as UL component parts, some are advertised as
Amerex type. None of these meet UL requirements and all of them voids
the Amerex extinguisher warranty and UL listing. DO NOT
SUBSTITUTE.
RECHARGE FIRE EXTINGUISHERS IMMEDIATELY AFTER ANY USE
REFERENCES IN THIS MANUAL: AVAILABLE FROM:
NFPA-10 Portable Fire Extinguishers National Fire Protection Association
1 Batterymarch Park, P.O, Box 9101
Quincy, MA 02269-9101
CGA C-1 Methods for Hydrostatic Testing of Compressed Gas Association, Inc.
Compressed Gas Cylinders 4221 Walney Road, 5
th
Floor
CGA C-6 Standard for Visual Inspection of Chantilly, VA 20151-2923
Compressed Gas Cylinders
AMEREX CORPORATION P.O. BOX 81 TRUSSVILLE, ALABAMA 35173-0081
Phone: 205/655-3271 Fax: 800/654-5980
e-mail: sales@amerex-fire.com Web Page: http://www.amerex-fire.com
Printed in U.S.A.
OM05603C Rev. 3/11
CARBON DIOXIDE HAND PORTABLE
FIRE EXTINGUISHERS
Model 322 5 LB Model 331 15 LB
Model 330 10 LB Model 332 20 LB

Questions and Answers

  • P
    paul79Jul 28, 2025
    What to do if there is a leak in the Amerex 322 cylinder?
    • H
      hinesdavidJul 28, 2025
      If your Amerex Fire Extinguisher cylinder is leaking, contact Amerex if it's under warranty. Otherwise, mark it as "Rejected" and remove it from service or return it to the owner.
  • J
    James MillerAug 2, 2025
    What to do if my Amerex 322 Fire Extinguisher leaks during discharge under discharge lever?
    • C
      Carla WardAug 3, 2025
      If your Amerex Fire Extinguisher leaks during discharge under the discharge lever, remove the valve assembly, downtube, spring, and valve stem assembly. Install a new valve stem assembly and check the valve seat for scratches or any foreign matter.
  • T
    tfranklinAug 8, 2025
    How to fix a leak at the safety relief nut on an Amerex Fire Extinguisher?
    • S
      Suzanne MorganAug 9, 2025
      To fix a leak at the safety relief nut of your Amerex Fire Extinguisher, remove the safety nut, disc, and gasket assembly. Replace it with a new Amerex P/N 04000 safety nut, disc, and gasket assembly. Tighten the assembly to 250 in-lbs of torque.
  • W
    William HaasAug 14, 2025
    What to do if my Amerex 322 has a leak through the valve?
    • M
      Melody WiseAug 15, 2025
      If your Amerex Fire Extinguisher is leaking through the valve, check the valve stem seating area for scratches or foreign matter. Clean the seating area with a toothbrush and soft cloth. Then, install a new valve stem assembly.
  • B
    Beverly StewartAug 21, 2025
    How to fix a leak at collar o-ring on Amerex 322 Fire Extinguisher?
    • D
      Daniel NguyenAug 21, 2025
      To fix a leak at the collar o-ring of your Amerex Fire Extinguisher, remove the valve assembly, clean the collar thoroughly, and install a new collar o-ring. Lubricate it with Visilox V-711 and reinstall the valve to a maximum of 100 ft-lbs torque.

Summary

Introduction and General Safety

Fire Extinguisher Compliance Standards

Adherence to NFPA-10 and local requirements for installation, inspection, and maintenance.

Professional Maintenance Recommendation

Recommends professional maintenance by trained individuals for safety and proper operation.

Use of Genuine Amerex Parts

Emphasizes using genuine Amerex parts to maintain warranty and UL listing; warns against substitutes.

Immediate Recharge After Use

Instruction to recharge fire extinguishers promptly after any discharge.

Five Year Limited Warranty

Inspecting the Extinguisher

Periodic Inspection Procedures

Outlines the monthly checks for extinguisher availability, condition, and charge level.

Operation of CO2 Extinguishers

Operator Training Requirement

Stresses the importance of training personnel on proper operation and fire fighting techniques.

CO2 Specific Warnings

Warns about oxygen deficiency in confined spaces and frostbite risk from skin contact with CO2.

Step-by-Step Operation Guide

Detailed instructions on how to operate the extinguisher, including aiming, sweeping, and stopping discharge.

Maintenance

Maintenance-Service Procedure

Step-by-step guide for thorough extinguisher maintenance, including cleaning and part inspection.

Recharge Procedure

Recharging Procedure Steps

Detailed steps for safely recharging the extinguisher with CO2, including weighing and leak checks.

Troubleshooting Guide

Leak Troubleshooting and Corrective Actions

Identifies common leak problems and provides specific corrective actions for valve and connection issues.

Parts List for 5 lb. Extinguisher

Parts List for 10-15-20 lb. Extinguishers

Comprehensive list of parts for 10, 15, and 20 lb. Carbon Dioxide extinguisher models.

Amerex 322 Specifications

General IconGeneral
TypeStored Pressure
ClassA:B:C
Extinguishing AgentMonoammonium Phosphate
Weight9.5 lbs
U.L. Rating3-A:40-B:C
Operating Pressure195 psi
Discharge Time14 seconds
Range12-18 ft
Capacity5 lbs