EasyManua.ls Logo

Amerex B260 - User Manual

Default Icon
5 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
PN 13259 04/2020
PART TITLE DATE CREATED CREATED BY REV.
13259 MANUAL OWNERS SERVICE WC 11/21/94 MS N
THIS DRAWING IS THE EXCLUSIVE AND CONFIDENTIAL PROPERTY OF AMEREX
CORPORATION. IT SHALL NOT BE DUPLICATED, USED OR DISCLOSED TO OTHERS
REV DRAWING CHANGE BY ECN# DATE
N PUBLISHER FILE CREATED; REFRESHED LAYOUT DESIGN CT B002026 4/29/20
COVER SHEET
DO NOT PRINT THIS PAGE FOR ACTUAL MANUAL. INTERNAL USE ONLY.
# NOTES
1 THIS COVERSHEET FOR INFORMATIONAL PURPOSES ONLY - DO NOT PRINT THIS PAGE IN MANUAL.
2 DESCRIPTION: MANUAL OWNERS SERVICE FOR WET CHEMICAL PORTABLES
3 ACTUAL PRINTED MATERIAL TO CONSIST OF ATTACHED
4 OVERALL SIZE OF PRINTED DOCUMENT PAGES: 8-1/2” X 11” ON 20 LB PAPER
5 PRINTED MATERIAL TO MATCH ATTACHED IN SADDLE STITCHED BOOKLET FORM
6 PRINT MATERIAL IS TO BE HOLE PUNCHED 3 EACH 1/4HOLES DOWN LEFT SIDE FOR STD 3-RING BINDER
7 CURENT REVISION DATE: 4/20

Questions and Answers

  • A
    Antonio ClarkJul 28, 2025
    What to do if Amerex Fire Extinguisher has restricted discharge stream?
    • J
      Jessica BarkerJul 28, 2025
      If you observe a restricted or intermittent agent discharge stream from your Amerex Fire Extinguisher, inspect the downtube strainer and discharge nozzle for any dirt, sediment, or obstructions. Clean or replace the affected parts as needed to restore proper function.
  • Y
    yglassAug 1, 2025
    What to do if Amerex Fire Extinguisher cylinder is leaking?
    • C
      Catherine CarlsonAug 1, 2025
      If you find a leak in the cylinder of your Amerex Fire Extinguisher, contact Amerex if the extinguisher is still under warranty. If it is not under warranty, mark it as "Rejected" and return it to the owner.
  • J
    Jesse RobbinsAug 6, 2025
    How to fix Amerex B260 leak around gauge threads?
    • N
      Nicole ParksAug 7, 2025
      If you notice a leak around the gauge threads of your Amerex Fire Extinguisher, remove the gauge. Then, reapply Teflon tape to the gauge threads and reinstall the gauge to ensure a tight seal.
  • M
    Marvin GarrisonAug 11, 2025
    How to replace defective gauge on Amerex B260?
    • M
      Mr. Benjamin Sanchez MDAug 11, 2025
      If the gauge on your Amerex Fire Extinguisher is defective, remove it and install a new gauge (PN 17420). Be sure to use Teflon tape on the gauge threads during reinstallation.
  • V
    Veronica AllenAug 17, 2025
    How to fix Amerex B260 Fire Extinguisher leak at collar O-ring?
    • F
      fberryAug 17, 2025
      To address a leak at the collar O-ring of your Amerex Fire Extinguisher, start by removing the valve assembly. Thoroughly clean the collar (knurled) nut and then install a new O-ring. Remember to lubricate the new O-ring with V-711 (PN 06247) before reassembling.
  • B
    Benjamin LyonsAug 21, 2025
    How to replace broken footstand on Amerex Fire Extinguisher?
    • A
      Andrea YoderAug 21, 2025
      To replace a broken footstand on your Amerex Fire Extinguisher, install a new footstand (PN 03109).

Summary

Cover Sheet Information

Manual Identification

Details the part number, title, creation date, creator, and revision of the manual.

Notes for Manual Printing

Provides instructions regarding the printing and content of the cover sheet and manual pages.

Wet Chemical Portable Extinguishers

General Safety and Maintenance Guidelines

Outlines installation, inspection, and maintenance requirements according to standards and professional practice.

References and Availability

Lists relevant standards and their sources for extinguisher maintenance and testing.

Amerex Corporation Service Disclaimer

States Amerex does not service extinguishers and the manual is a guide for qualified personnel only.

Extinguisher Inspection and Maintenance

Inspection Procedure

Details the 'quick check' items for extinguisher readiness as per NFPA 10.

Maintenance Service Procedure

Describes the annual thorough check, including cleaning, part inspection, weighing, and hydrostatic testing.

Recharging Procedures

Recharge Process Overview

Defines recharging as agent and expellant replacement, with crucial safety warnings for depressurization and pressurization.

Step-by-Step Recharging

Provides detailed instructions for disassembling, cleaning, replacing parts, and refilling extinguishers.

Troubleshooting and Parts

Troubleshooting Guide

Identifies common problems with extinguishers and their corrective actions, emphasizing depressurization before repair.

Replacement Parts Information

Directs users to the Amerex website for a parts book to order replacement components.

Amerex B260 Specifications

General IconGeneral
ModelB260
Capacity2.5 lbs
AgentABC Dry Chemical
Operating Temperature-65°F to 120°F
Operating Pressure100 PSI
Cylinder MaterialSteel
Discharge Time8 sec
Range10-15 feet
ClassC
Fire Rating10-B:C

Related product manuals