Sequoia / Tahoe Series User Manual California Instruments
M447352-01 REV-A 159
The user-defined waveforms could be selected from up to fifty
waveforms in one of four groups (group 0-3, totaling 200
waveforms) that are active. The waveform group that is active at
the power-on of the unit could be selected with the SCPI
command, PONSetup:WGRoup <n>, through the digital
interface. For information on generating user-defined waveforms
and their selection, refer to the Sequoia Series Programming
Manual P/N M447353-01 or the Sequoia Virtual Panels GUI; refer
to AMETEK PPD website, www.programmablepower.com, to
download the latest version.
Figure 5-94. Waveform Settings
RANGE Selects the 166 VAC or 333 VAC range for AC-mode and
(AC+DC)-mode, and 220 VDC or 440 VDC range for DC-mode
operation. The output must be turned off for a change in range to
be executed. The default is low-range, 166 VAC.
Figure 5-95. Range Settings
MODE SETTING Selects the mode of operation of output voltage: either AC only,
DC only, or AC with a DC offset, AC+DC. This selection also
determines the available output voltage ranges: 166/333 V(RMS)
in AC and AC+DC modes, and 220/440 VDC in DC mode. The
output must be turned off to change this setting. The default is
AC.