Sequoia / Tahoe Series User Manual California Instruments
170 M447352-01 REV-A
External: Enables the external analog interface programming
input that sets waveform and amplitude.
RPV: Enables the external analog interface programming input
that sets the amplitude, while the internal waveform generator is
used to set the waveform.
Figure 5-117. PONS Reference Settings
PONS PHASE NUMBER PONS menu: Selects the output configuration, either 1-Phase or
3 Phase, for 3-Phase models; the default is 3-Phase.
Figure 5-118. PONS Phase Number Settings
CLOCK MODE Selects the source for the synchronization of the output
frequency; default is Internal:
Internal: Derives synchronization from the internal waveform
generator.
SYNC: Derives synchronization from the user interface SYNC
signal; available only in a Standalone unit or Leader unit.
External: Derives synchronization from the external Clock/Lock
interface; available only in the Auxiliary unit with the Clock/Lock
option, LKS; for multi-phase operation, the Auxiliary unit must
have the setting at External.