Sequoia / Tahoe Series User Manual California Instruments
34 M447352-01 REV-A
2.33 XVC - 666 Option Specifications
The –XVC option provides an AC only output range of 0 to 666 Vac L-N. Common specifications for all
models are given in Table 2-16. Current ratings for different power models for 3-phase and 1-phase mode
are in Table 2-17 and Table 2-18 respectively. In -XVC option range only Source and SINK-grid simulator
operating modes are supported (SINK-Electronic Load operating mode is not supported). Output current
limit characteristics are shown in Figure 2-5.
All Models
Working mode AC Mode
AC Output phase Voltage 0 – 666 V
Voltage Resolution 0.1 V
Voltage Programming
Accuracy
± 0.25% of Full Scale
Output Coupling AC coupled
Frequency range with Standard option: 45 Hz – 550 Hz
with –HF option: 45 Hz – 905 Hz (see also –HF
option specification.)
Table 2-16: Common Output electrical specifications for XVC – 666 V option
Model
No of
chassis
Output Power (KVA) AC mode Output Current,
Full-Scale ( Per Phase)
AC mode RMS (A) Peak (A)
SQ0090/
TA0090
2 x SQ0045
2 x TA0045
1 x SQ0090
1 x TA0090
90 45 135
SQ0180/
TA0180
2 x SQ0090
2 x TA0090
180 90 270
SQ0270/
TA0270
3 x SQ0090
3 x TA0090
270 135 405
SQ0360/
TA0360
4 x SQ0090
4 x TA0090
360 180 540
SQ0450/
TA0450
5 x SQ0090
5 x TA0090
450 225 675
SQ0540/
TA0540
5 x SQ0090
5 x TA0090
540 270 810
Table 2-17 : Phase output Current and Power specifications for -XVC 666 option-Three
phase
Model
No of
chassis
Output Power
(KVA)
AC mode Output Current,
Full-Scale (Per Phase)
AC mode RMS (A) Peak (A)
SQ0090/
TA0090
1 90 135 405