UPS + Isolation Transformer        User Manual 
  
© 2020 AMETEK Electronic Systems Protection | Technical Support: 1-800-645-9721 | surgex.com        13                     
 
 
 
 
Load Monitor 
The Load Monitor is a six-segment LED display that shows the current load 
percentage. 
The  first 5 
LED’
s
 
each 
indicate approximately 20%  load,  with 
the
 
6th red LED showing the UPS is overloaded. 
 
 
Battery Charge Monitor 
The  Battery 
Charge 
Monitor is a 
five-segment 
LED display  that 
shows the charge 
capacity 
of the  internal  battery from zero  to 100%.  Each LED 
indicates 
approximately 
20%  of full 
charge.
 
 
Site  Wiring Fault Indicator  – (120  VAC 
models only)
 
The “SF” symbol will be displayed on the front panel of the UPS if it is connected to an 
improperly wired AC receptacle.  This is to indicate a missing safety ground wire or a reversal in 
phase and neutral wiring.  If the “SF” is 
displayed 
on the  front panel you should 
contact 
a 
qualified 
e
lectrician 
immediately. 
 
NOTE: 
Do not operate the UPS if the Site Wiring Fault LED is illuminated. When lit, the LED 
is indicating a wiring condition, which may represent a 
hazard 
of fire or 
electrocution.  
In addition, improper wiring may 
create 
reliability problems for both 
the UPS and the connected system.  Never use a 3-blade to 2-blade adapter (often 
called a “cheater”) to power UPS. These devices remove the safety ground connection 
to the UPS and will cause the Site Wiring Fault LED to illuminate.