24
UPS + Isolation User Manual
© 2020 AMETEK Electronic Systems Protection | Technical Support: 1-800-645-9721 | surgex.com
Model #: ABCE1442-11R / Part #:UPS-1440-Li-ISO
Rack Mount
UPS
Specifications
Front
Panel Controls
Po wer
On/Off
Test
Load Leve l L ED
Gauge
Battery Ch arge L ED
Gauge
Voltage Mana ger Boost
LED
Voltage Output On
LED
Voltage Mana ger Bu ck
LED
On Battery
LED
Rep lace Batter y
LED
Over load
LED
Fault Co de
LED
System Over Te mp erature
LED
Rear
Panel
Information
and Controls
Integrated Switched Power Distribu tion
Unit
(Requires SNMP
/
Web
Card)
Configuration Manager DIP
Switches
Comm un ica tion s Ma nager DB9 Port , USB
Port
Circuit Bre aker ( AC an d
DC)
AC Inlet
Module
Comm un ica tion Opt ion Slot: SNMP
/
Web Card,
Isolated
Rela y Contacts Card, or Re mote Of f
Card
DC External Battery Ca bine t
Connector
Fan (For ced
Cooling)
Internal
Batteries
User Hot-S wappable (See Instruction
Manual)
Type: 12 Volt, High Rate
23W
Qua ntit y: 4
Batteries
Rec harge Time: 6 Hours to 80 %, 24 Hours to Full
Charge
(For I ntern al Batter ies
Only)
Environmental
Temperature: 0 -
+40
(32
to
104
)
Operating
-20 to
60
(-40
to
140
)
Shipment/
Stora ge
Humidity:
5 to 90 % Non- Condensing ( Operat ing,
Shipment/Storage)
Altitude:
3,000m ( 10,000 ft) m ax.
Operating;
12,000 m (40,000 ft) max .
Shipment/Storage
Safety
Agency and
EMC
Compliance:
All Units are L isted by UL an d Marked With the UL/cUL
Marking
Standard
UPS:
Products
Listed
to:
UL1 778 5th
Edition
CS A 22.2 Nos.
107.3-14
Products in
Comp lianc e
with:
FCC- Part 1 5, Subp art B, Section s 15.107b &
15.109b
Cla ss A Dig ital
Device*
CISPR11:2 009, A1; 2010, Class
A*
IEC61 000-4-2, Ele ctrost atic
Discharge
IEC61 000-4-3, Radiated Electro magn etic Fiel d
Immunity
IEC61000-4-4, Electrical Fa st Tran sient/ Burst
Immunity
IEC61 000-4-5, Surge
Immunity
IEC61 000-4-6, I mmunity to Conducted Ra dio
Frequency
Disturbances
IEC61 000-4-8, Power Frequ ency Magnetic Fi eld
Immunity
IEC61000-4-11, Voltage Dip s, Sh ort Interru ption s
and
Voltage
Variations
*Note: Class B is Ava ila ble as an
Option
Pleas e Cons ult Your Surge X Sales
Representative
RoHS
Compliance:
All Produ cts (Standar d and Medi cal) are Ro HS
Compliant
1440
VA MODELS TYPICAL RUN-TIMES
(MINs)
10%
(130W)
20%
(259W)
30%
(389W)
40%
(518W)
50%
(648W)
60%
(778W)
70%
(907W)
80%
(1036W)
90%
(1166W)
100%
(1296W)
Internal Batteries
Only
90
38
20
12
9
6
5
4
2.8
2.5
Internal + 1)
E4804-12
480
183
110
72
59
51
35
30
25.8
24.5
Internal + 2)
E4804-12
870
328
200
132
109
96
65
56
48.8
46.5
Internal + 3)
E4804-12
1260
473
290
192
159
141
95
82
71.8
68.5
Internal + 4)
E4804-12
1650
618
380
252
209
186
125
108
94.8
90.5
Internal + 5)
E4804-12
2040
763
470
312
259
231
155
134
117.8
112.5
Internal + 6)
E4804-12
2430
908
560
372
309
276
185
160
140.8
134.5
Internal + 7)
E4804-12
2820
1053
650
432
359
321
215
186
163.8
156.5
Internal + 8)
E4804-12
3210
1198
740
492
409
366
245
212
186.8
178.5
NOI SE REJECTION-IS OLATI ON: With unit under po wer and an ANSI/IE EE C62.41 Cat. A pulse applied either nor mal or co mmon mode at the input,
the
noise output voltage will be less than
10V nor mal mode an d le ss t han 0 .5 V co mmon mo de in all f our qu adrants ( CM- NM, NM- NM, CM- CM,
NM-CM).
SURGE VOLTAGE WITHSTAND CAPABILITY: Tested under po wer to ANSI/IE EE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A
-
6000 V @ 200
amps,
0.5 usec riset ime, 10 0 k HZ decay,
Cat. B
-
6000 V @ 500 a mps, 0.5 use c risetime, 1 00 kHZ
decay.
Warranty/Suppo rt: SurgeX warrants the electronics and transformers used in its uninterruptible po wer managers to be free from defect s in material s and
work
manship for
a
period of five
years
from
the date
of shipment. Batteries
are
warranted for
a
period of two
years
from
the date
of
shipment. For service
or
support
on
any SurgeX product, please contact SurgeX Technica l
Support at (800) 645-9721 or visit the SurgeX website at
www.surgex.com.
Battery Life Disclaimer: SurgeX
s standard
battery warranty applies only
to UPS and
UPS products which
are
continuously
connected
to AC mains
power,
except during utility power
outages. Products which are regularly and intentionally disconnected fro m AC mains power will experience battery discharge/charge cy cles potentially far more numerous than those for which the
battery wa s designed. As a result, products used in such applications will experience substantiall y
reduced
battery life. For
that reason,
SurgeX
s standard
battery warranty
does
not apply
for applications in which
the UPS or
UPS product
is
regularly
and
intentionally disconnected from AC main s po wer. SurgeX UPS and UPS products used in such applications shall receive a 90
day warranty on
batteries.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ametek SurgeX UPS-1440-Li-ISO and is the answer not in the manual?

Ametek SurgeX UPS-1440-Li-ISO Specifications

General IconGeneral
BrandAmetek
ModelSurgeX UPS-1440-Li-ISO
CategoryUPS
LanguageEnglish

Related product manuals