A properly sized boiler is the key to pasteurizing in a quick timely manner.
Since the maximum tank jacket pressure is 70 PSI and the maximum flow-
rate is 50 GPM, we recommend using a hot water or low-pressure steam
boiler. Check the boiler regulations in your state before purchasing a boiler.
Tank Size
in Gallons
Side Jacket
in Gallons
Side Jacket
in Sq. Ft.
Bottom Jacket
in Gallons
in Sq. Ft.
BTU's
Required
50 1.8 12 1.4 7
100,000
75 2 13 1.4 7
150,000
100 3 18 1.4 7
200,000
150 4 26 1.4 7
265,000
200 5 33 1.4 7
350,000
300 7 42 2 11
525,000
400 8 48 2 13
600,000
500 9 54 3 17
750,000
600 10 60 3 18
900,000
800 11 68 3 19
1,200,000
1,000 12 82 3.5 20
1,500,000
1,200 16 136 4 22
1,800,000
1,500 18.5 166 4.5 24
2,250,000
2,000 22 204 5 26
3,000,000
Note: Figures below are based on a standard tank and may vary if tank dimensions
change.
Sizing your Boiler