26
Andover Controls
Wire Gauges and Corresponding Maximum Runs for
Sensing Temperatures Up to 70 °F (21 °C)
Gauge
1/2
°F (.28 °C) Error 1/4
°F (.14 °C) Error 1/10
°F (.06 °C) Error
#14 26,700 ft. 13,300 ft. 5,300 ft.
2.5 mm
2
8150 m 4000 m 1600 m
#16 16,700 ft. 8,300 ft. 3,300 ft.
1.5 mm
2
5120 m 2500 m 1000 m
#18 10,500 ft. 5,200 ft. 2,100 ft.
1.0 mm
2
3200 m 1600 m 640 m
#20 6600 ft. 3,300 ft. 1,300 ft.
0.5 mm
2
2000 m 1000 m 400 m
#22 4,100 ft. 2,000 ft. 800 ft.
0.35 mm
2
1250 m 600 m 250 m
Wire Gauges and Corresponding Maximum Runs for
Sensing Temperatures Up to 100 °F (38 °C)
Gauge
1/2
°F (.28 °C) Error 1/4
°F (.14 °C) Error 1/10
°F (.06 °C) Error
#14 12,600 ft. 6,300 ft. 2,500 ft.
2.5 mm
2
3800 m 1900 m 760 m
#16 7,900 ft. 3,900 ft. 1,500 ft.
1.5 mm
2
2400 m 1200 m 450 m
#18 5,000 ft. 2,500 ft. 1,000 ft.
1.0 mm
2
1500 m 760 m 300 m
#20 3,100 ft. 1,500 ft. 600 ft.
0.5 mm
2
950 m 450 m 180 m
#22 1,900 ft. 900 ft. 300 ft.
0.35 mm
2
580 m 275 m 90 m
UI-8-10