Continuum I/O System Reference
27
Wire Gauges and Corresponding Maximum Runs for
Sensing Temperatures Up to 150 °F (65 °C)
Gauge
1/2
°F (.28 °C) Error 1/4
°F (.14 °C) Error 1/10
°F (.06 °C) Error
#14 4,100 ft. 2,000 ft. 800 ft.
2.5 mm
2
1250 m 600 m 240 m
#16 2,600 ft. 1,300 ft. 500 ft.
1.5 mm
2
800 m 400 m 150 m
#18 1,600 ft. 800 ft. 300 ft.
1.0 mm
2
500 m 240 m 90 m
#20 1,000 ft. 500 ft. 200 ft.
0.5 mm
2
300 m 150 m 60 m
#22 600 ft. 300 ft. 100 ft.
0.35 mm
2
180 m 90 m 30 m
UI-8-10
Technical Manuals Online! - http://www.tech-man.com