Andover Controls
Voltage Output
The voltage output is a ground-referenced signal with a range of 0-10VDC. The
maximum output current is 5mA (2,000 ohms minimum resistance). Ensure that the
device being connected is either floating or at the same ground potential as the controller.
Configure the output point with an Electrical Type of
Voltage
.
Connect the device across the following terminals:
Note: The load resistance (of the external device) must be greater than or equal to 2 K
.
OUTx V
GND
Device
Load
Resistance
OUTx I
2K
AO-4-8