Continuum I/O System Reference
79
Current Output
The current output is a current-sourcing, ground referenced circuit. This output can
source 0 - 20 mA with a maximum load impedance of 650 ohms.
Configure the output point with an Electrical Type of
Current
.
Connect the device across the following terminals:
Note: The load resistance (of the external device) must be less than or equal to 650
.
OUTx V
GND
Device
Load
Resistance
OUTx I
650
AO-4-8