CHAPTER 4: MESSAGES
17
PowerView
Message
Meaning Corrective Action
Redundancy
Restored.
Power module redundancy loss occurred
and was restored. Either additional
modules have been installed or the load
has been reduced.
Load is No
Longer above
Alarm
Threshold.
The load exceeded the load alarm
threshold. The situation has been
corrected because either the load
decreased or the threshold was
increased.
General
Status
(continued)
Min Runtime
restored.
The system runtime dropped below the
configured minimum runtime and was
restored.
Either additional battery modules were
installed, the existing battery modules
were recharged, the load was reduced,
or the threshold was raised.
No corrective action
necessary.
Bad Battery
Module.
A battery module failed and requires
replacement.
Bad Power
Module.
A power module failed and requires
replacement.
Intelligence
Module is
installed and
failed.
The intelligence module in the lower IM
slot has failed.
Module
Failure
Redundant
Intelligence
Module is
installed and
failed.
The intelligence in the upper IM slot has
failed.
Refer to installing modules in
the Physical Installation or
Service Manual.
Load is above
kVA alarm
threshold.
The load has exceeded the user
specified load alarm threshold.
Option 1: Reduce the load.
Option 2: Use the PowerView
interface to raise the alarm
threshold.
Threshold
Alarm
Redundancy
has been lost.
The UPS no longer detects redundant
power modules. Either power module(s)
failed or the load increased.
Option 1: If possible, install
additional power modules.
Option 2: Decrease the load.
Option 3: Disable the
redundancy alarm by setting
redundancy to zero.
(Startup>Setup>Alarms>
Redundancy>Zero)