Machine Usage
8
G5TWIN OPERATION MANUAL
© 2016 APPION INC. - ALL RIGHTS RESERVED
PREPARING FOR OPERATION
Every recovery procedure starts with the same ve basics:
Remove any access valve cores from the AC/R System access ttings with a Valve Core Removal Tool;
Remove any core depressors from the hose ttings. Do not use quick disconnect” or auto-shutohose
connections for refrigerant recovery, as this can bring the recovery to a halt. Use only ball valves for low-loss.
Use the shortest length of 3/8”-diameter hoses possible on every connection. Even with 1/4” ttings, the
larger hose diameter can deliver better performance during recovery.
Purge the hoses of non-condensables as you connect the hoses, as needed, using best practices to minimize
any refrigerant release (aka de minimis”). Excess non-condensables can cause tank overheating, and may
contaminate recovered refrigerant.
Connect the G5Twin to a grounded power source for the proper voltage of the machine (115v/230v). If using
an extension cord, follow the cord sizing guidelines on Page 4.
For additional refrigerant recovery tips, see pages 14-17.
G5TWIN OPERATIONAL LAYOUT
Horizontal Knobs: Valves Closed Vertical Knobs: Valves Open
Diagram 2
Diagram 3