In Parallel Mode, each instruments’ LINE output must be connected together at the
load. If you are linking two sources there will be two line connections. If you are
linking three sources there will be three line connections. (See Figure 4)
Also, each instruments’ NEUTRAL output must be connected together at a load. If
you are linking two sources there will be two neutral connections. If you are linking
three sources there will be three neutral connections. (See Figure 4)
(Figure 4)
Once all the linking cables and conductor connections have been made, you can
power up each individual 300XAC via the Power Switch on the front panel. Upon
power up, the 300XAC will go through an initialization screen to verify that the
additional sources are interconnected via the linking cable. If there is a proper
connection, a message will appear acknowledging that additional 300XAC sources
are linked and prompting the user to enable the additional sources.
LINKINGSOURCES
FUNCTIONMODE
The FUNCTION mode changes the output voltage configuration.
Power up all instruments. From the Set screen press the “<more>” soft key and in the
next screen press the “System” soft key.
In the System Parameters Menu, you can use the up or down arrow soft keys to
highlight the FUNCTION parameter.
When the FUNCTION parameter is highlighted, press the “Edit” soft key and use the
“Change” soft key to select the FUNCTION mode to “PARALLEL”.
To save changes made, press the “Enter” soft key and then press the “Exit” soft key
two times to get back to the Set screen.
8.
Load
Line 1
Neutral 1
Line 2
Neutral 2
Line 3
Neutral 3
MASTER
SLAVE
SLAVE