Do you have a question about the Areva MiCOM P922 and is the answer not in the manual?
Rated Voltage | 24-250 V DC / 48-265 V AC |
---|---|
Rated frequency | 50/60 Hz |
Binary inputs | 8 |
Display | LCD |
Communication ports | RS485 |
Communication Protocols | IEC 61850, DNP3, Modbus |
Protection Functions | Overcurrent, Earth Fault |
Mounting | Panel |
Inputs | Binary |
Outputs | Binary |
Enclosure | IP54 (front), IP30 (rear) |
Provides essential safety instructions for handling and operating the MiCOM relay to prevent damage and ensure user safety.
Guides the user on how to navigate the relay's menu structure, including password protection and setting changes.
Outlines the setting ranges for various protection functions like undervoltage, overvoltage, and frequency, including time delays and characteristics.
Covers safety aspects, specifically the Low Voltage (safety and insulation) Directive compliance.
Explains the configuration and HMI descriptions for various protection functions including undervoltage, overvoltage, residual overvoltage, negative sequence, and positive sequence undervoltage.
Details the MODBUS protocol characteristics, network features, connection parameters, message validation, and functions supported by MiCOM relays.
Explains the K-Bus protocol, its transmission layer, connection, and the Courier language, including relay database organization and event lists.
Describes methods for mounting MiCOM relays, including rack mounting with specific frames and panel mounting with fixing details.
Lists the minimum and optional equipment required for commissioning MiCOM relays, including test sets, multimeters, and PCs.
Details essential checks for the relay before and after applying power, covering visual inspection, wiring, insulation, and operational status.
Ensures that all protection, control, and logic equation settings are correctly applied to the relay, providing methods for applying and checking them.
Provides detailed test procedures and expected results for phase overvoltage and undervoltage protection functions using definite and inverse time delays.
Describes how to test the under/overfrequency protection function, including relay parameter configuration and test examples.
Explains how to test the rate of change of frequency function, including wiring diagrams, relay parameters, and test examples.
Recommends periodic monitoring and maintenance for protective relays to ensure correct operation, covering checks for alarms, inputs, outputs, and accuracy.
Provides a template for recording commissioning details, including date, operator, substation, circuit, protection relay information, and safety checks.
Details checks to be performed on the relay before and after energization, covering visual inspection, wiring, insulation, watchdog contacts, and auxiliary supply.
Guides the verification of application-specific settings, including programmable logic equations and their validation.
Describes on-load checks for test cables, wiring, and voltage inputs, ensuring correct operation and measurements.
Details the configuration of logic inputs, timer delays in logic equations, and the mapping of functions to LEDs and output relays.
Provides tables for setting parameters of various protection elements including undervoltage, overvoltage, residual overvoltage, negative sequence, positive sequence, and frequency protections.