EasyManuals Logo

Argo AW735CLF Service Manual

Argo AW735CLF
39 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
6) TROUBLESHOOTING
6-1 CHECK BEFORE AND AFTER «TROUBLESHOOTING»
(A) Check power supply wiring.
• Check the power supply wires are correctly connected.
(B) Check power supply.
• Check that voltage is in specified range (±10% of the rating).
• Check that power is being supplied.
• WARNING: If the following troubleshooting must be done with power supplied,
be careful not to touch any uninsulated live part that can cause
eletric shock
6-2 CIRCUIT BREAKER TRIPS OR FUSE BLOWS.
• When circuit breaker is set to ON, it trips in a few moments. Resetting is not possible.
• Measure insulation resistance. There is a possibility of ground fault.
If resistance value is 1 Mohm or less, insulation is defective.
6-3 CIRCUIT BREAKER TRIPS IN SEVERAL MINUTES
AFTER TURNING AIR CONDITIONER ON.
1 • There is the possibility of short circuit.
30

Other manuals for Argo AW735CLF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Argo AW735CLF and is the answer not in the manual?

Argo AW735CLF Specifications

General IconGeneral
BrandArgo
ModelAW735CLF
CategoryAir Conditioner
LanguageEnglish

Related product manuals