2-3.Other Component Specifications
2-3-1.Indoor Unit
5
<AWR218CLE>
<AWR218CLE>
<AWR218CLE>
Thermistor (Room sensor TH2) KTEC-35-S6
Resistance kΩ 10°C10.0 ±4% 30°C 4.0 ±4%
15°C 7.9 ±4% 35°C 3.3 ±4%
20°C 6.3 ±4% 40°C 2.7 ±4%
25°C 5.0 ±4% 50°C 1.8 ±4%
Thermistor (Coil sensor TH1) PBC–41E–S4
Resistance kΩ –20°C40.1±5% 20°C 6.5±5%
–10°C24.4±5% 30°C 4.4±5%
0°C15.3±5% 40°C 3.0±5%
10°C 9.9±5% 50°C 2.1±5%
Transformer (TR) ATR-H85
Rating Primary AC 230V, 50Hz
Secondary 11V, 0.727A
Capacity 8VA
Coil resistance Ω(at 21°C) Primary (WHT – WHT): 214 ±10%
Secondary (BRN – BRN): 1.58 ±10%
Thermal cut-off temp. 145°C, 2A, 250V