SPECIFICATIONS FOR ARGUS TECHNOLOGIES’ SWITCHED MODE RECTIFIER MODEL RST 48/30
Input
Voltage: 92 to 132VAC (57-63 Hz)
184 to 264VAC (47-63 Hz)
Current: 10.2 Amps (240VAC nominal) @ 1698 Watts
20.4 Amps (120VAC nominal) @ 1698 Watts
Power Factor: .90 Lagging 0-100% load
T.I.F.: Less than 120 at 100% load (current)
Efficiency: 88% min. 40-100% load
Hold-over Time: 30ms from loss of 240VAC line
Source Impedance: 5% inductive or resistive
Soft Start: 33% per second
Start Delay: 0-90 sec. (10 second increments)
Recommended Feeder Breaker: 30 Amps or greater (120VAC)
15 Amps or greater (240VAC)
Breaker Rating: 30 Amp; 10,000 Amp interrupting capacity at 250VAC (120VAC)
15 Amp; 10,000 Amp interrupting capacity at 250VAC (240VAC)
Miscellaneous
Acoustic Noise: 45dBa at three feet
Weight: 40 lbs (18.2 kg)
Size: 7.00”H x 17”W x 15” (17.7cm H x 43.2cm W x 38.1cm D)
Recommended Connection Wire Sizes (as per UL)
Ambient Temp=30 deg C Input: #12 AWG
Output: #10 AWG
Ambient Temp=50 deg C Input: #10 AWG
Output: #8 AWG
Environmental
Temperature: 0 to 50 deg. C [operating](32 to 122 deg. F)
40 to +70 deg. C [storage](-40 to +158 deg. F)
Humidity: 0 to 90% non-condensing
Elevation: -500 to +2800m above sea level
(derate max. ambient to +40 linearly at 3100m)
ARGUS TECHNOLOGIES 010-006-B1 Rev B Page 2 of 2