GB - 23
technical adjustments
TABLE OF PARAMETERS
CABLED AND WIRELESS VERSIONS
- Hold + down for 5 seconds. The display will alternate between the software version and
modification index.
- Press “OK” to enter the settings menu.
- Press +” and “-” to scroll through the parameters.
- Press "OK" button to select a parameter.
Par. Description Default
CF01 Room temperature correction (range +/-5°C) 0°C
CF11
0: Display OFF after 10s
1: Display always on
1
CF12
0: Backlight o
1: Backlight OFF after 5s of inactivity
1
WIRELESS VERSION
- Hold + down for 5 seconds. The display will alternate between the software version and
modification index.
- Hold “+” down for 5 seconds again to enter the technical parameters menu; parameter “rF01”
will display
- Press “OK” to enter the settings menu.
- Press “+” and “-” to scroll through the parameters.
- Press "OK" button to select a parameter.
Par. Description Default
rF01 Detect device (0 - 15)
rF02 Associate zone (1 - 6)
rF03 Signal level (0 - 4)
rF04 Association (0 - 1)
TABLE OF ERRORS
Error Cause Solution
Err – Ebus
Zone association error: the
zone associated with the
device is already assigned
Check the installed room sensors. Associ-
ate a dierent zone
Err – rout
Radio communications error:
the room sensor is out of
range of the receiver or aerial
Check the signal strength with parameter
“rF03”
Use an aerial.
Reposition the room sensor.
Repeat the association procedure
- - -
Err
The room sensor is damaged Replace it