EasyManua.ls Logo

Ariston Andris R10 - Page 9

Ariston Andris R10
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 / EN
2.8 m (10 l) or 4.2 m (15 l) of 15 mm
pipe is required for expansion
DISCHARGE
COLDHOT
SUPPLY TO OTHER
PARTS OF PLUMBING
SYSTEM
DIELECTRIC
JUNCTIONS
PRESSURE RELIEF
VALVE 6 BAR
NEAREST COLD
WATER DRAWOFF
ISOLATING VALVE
FIXED JUMPER OR 1/4 TURN BALL TYPE
COLD WATER
MAINS
DISCHARGE
COLDHOT
SUPPLY TO OTHER
PARTS OF PLUMBING
SYSTEM
KIT A NON-RETURN VALVE
DIELECTRIC
JUNCTIONS
PRESSURE RELIEF
VALVE (6 BAR)
NEAREST COLD
WATER DRAW-OFF
ISOLATING VALVE
(FIXED JUMPER OR 1/4
TURN BALL TYPE)
KIT B PRESSURE REDUCING
VALVE (SET AT 3.5 bar)
KIT A EXPANSION VESSEL
(CHARGE AT SET 3.5 bar)
COLD WATER
MAINS
Fig. 1 (Note: this system is not suitable for 30L)
Fig. 2 The tundish must be installed away from electrical devices. (Models 10/15L)
The water connection may be carried out as per the following.
1) Using the feed pipe to accommodate expansion
(Schedule 2, Section 6: Paragraph 15 of the Water Supply (Water Fittings) Regulations 1999 and
the Water Byelaws 2000, Scotland) (Fig. 1).
Do not fit any stop cocks or isolating valves within the distance required for expansion. If a pressure
reducing valve is needed, due to a mains pressure of over 3.5 bar, an expansion control kit must be
fitted regardless of expansion pipework installed. The expansion distances quoted are for 15mm
pipes and can be approximately halved for 22mm pipes.
2) Using a set of expansion controls (Fig. 2 & 3).

Related product manuals