100 /
MENU
SUB-MENU
PARAMETER
DESCRIPTION RANGE FACTORY SETTINGS
19 1 0 Connectivity Status
OFF
Initialization
Idle
Acess Point initializing
Acess Point mode on
Station Mode - Connecting
Station Mode - Connected
Station Mode - Provisioning
Station Mode - Server Connected
Wifi error
19 1 1 Signal Level
19 1 2 Active Status
Not provisioned
Provisioned - Not active
Active
19 1 3 Serial Number
19 1 4 SW Upgrade Status
Initialization
Waiting for Update
Updating Micro 1
Updating Micro 2
19 1 5 On line outdoor temperature OFF – ON OFF
19 1 6 On line weather data OFF – ON OFF
19 2 Reset Menu
19 2 0 Re-configuration Resettare? OK=Yes, esc=No
20 Buer
20 0 Configuration
20 0 0 Buer Activation OFF - ON OFF
20 0 1 Buer charge mode
Partial charge (1 sensor)
Full charge (2 sensors)
Partial charge (1
sensor)
20 0 2 Buer setpoint temp. hysteresis 0 ÷ 20°C 5°C
20 0 3 Buer setpoint temperature heating [20 ÷ 70°C] 40°C
20 0 4 Buer setpoint temperature cooling [5 ÷ 23°C] 18°C
20 0 5 SG Ready Buer setpoint [20 ÷ 70°C] 40°C
20 0 6 Oset of PV Integration Setpoint [0 ÷ 20°C] 0°C
20 0 7 Buer Setpoint mode
Fixed
AUTO function
Fixed
20 1 Diagnostics
20 1 0 Buer temperature sensor (Low)
only reading
20 1 1 Buer temperature sensor (Mid) (not used)
only reading
20 1 2 Buer temperature sensor (High)
only reading
20 1 3 Buer charge request OFF – ON
only reading
20 2 Statistics
20 2 0 Buer charge hours Heating (/10)
only reading
20 2 1 Buer charge hours Cooling (/10)
only reading