DESCRIPTION RANGE FACTORY SETTINGS
5 5 8 Target deltaT for pump modulation cooling [-5; -20°C]
-5°C
12 HYBRID EVO 2 Param
12 0 User Parameters
12 0 0 Hybrid Mode
Auto
Only Boiler
Only HP
Auto
12 0 1 Energy Manager Logic
Max Saving
Max Ecology
Max Ecology
12 0 2 ECO / COMFORT
ECO PLUS
ECO
MEDIO
COMFORT
COMFORT PLUS
MEDIO
12 0 3 AUTO function
Absent
Present
Present
12 0 4 Quiet Mode Activation OFF - ON OFF
12 0 5 Quiet Mode start time [hh:mm] 00:00 - 24:00 22:00
12 0 6 Quiet Mode end time [hh:mm] 00:00 - 24:00 06:00
12 0 7 Photovoltaic Integration
Not active
Active
Not active
12 0 8 PV Delta T DHW setpoint temp. 0°C - 20°C 0°C
12 1 Input Output Configuration
12 1 0 HV Input 1
Not Defined
Absent
EDF
SG1
External switch o signal
EDF
12 1 1 HV Input 2
Not Defined
Absent
DLSG
SG2
Absent
12 1 2 HV Input 3
Not active
PV Integration Active
Not active
12 1 3 AUX Input 1
None
Humidistat sensor
None
12 1 4 Uscita AUX 1 (AFR)
None
Fault alarm
Humidistat alarm
External heat request
Cooling request
DHW request
None
12 1 5 Uscita AUX 2
None
Fault alarm
Humidistat alarm
External heat request
Cooling request
DHW request
None
12 1 6 AUX P2 circulator setting
Auxiliary circulator
Cooling circulator
Buer circulator
Auxiliary circulator
12 2 Energy manager parameter 1
12 2 0 Hydraulic scheme
None
WHB Combi
WHB + Tank
None
12 2 1 FlowT HP Oset 2°C - 10°C 2°C
12 2 2 Text for Boiler disabling Text for HP disabling - 0°C - 40°C 35°C
12 2 3 Text for HP disabling - 20°C - Text for Boiler disabling -20°C
12 2 4 External temperature correction -3°C - +3°C 0°C