EasyManua.ls Logo

Ariston NIMBUS COMPACT S NET - Internal Unit Electrical Connection; Power Supply and Protection Recommendations; Internal Unit Electrical Connection Data

Ariston NIMBUS COMPACT S NET
100 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
68 / GB
Power supplies of the indoor and the outdoor units are to be respectively connected to a Residual Current operated Circuit-Breaker
(RCCB) with threshold of 30mA. For inverter driven units (outdoor unit), It is advisable the use of type B residual current device for 3Ph
power supplies and type B or F for 1Ph power supplies (depending on the electrical system to which it is connected). For the units
without inverter, (indoor units) a type A Residual current device is sucient. The type of connection must in any case be carried out in
a workmanlike manner by qualified personnel in compliance with the national regulations in force.
INTERNAL UNIT
FS 40 - 50 S FS 70 S FS 90 110 S
Electrical supply V - ph - Hz
230 - 1 -50 230 - 1 -50 400 - 3 -50 230 - 1 -50 400 - 3 -50
Admitted voltages field V
196 ÷ 253 196 ÷ 253 340 ÷ 440 196 ÷ 253 340 ÷ 440
Rated power input kW
4 4 4 6 6
Max current A
19.1 19.1 9.6 30 9.6
Cutout - Circuit Breaker size
A
25 - C type 25 - C type
12 - C type
13 - C type
32 - C type
12 - C type
13 - C type
Dierential Circuit Breaker size (RCCB) mA
30 - A type
Supply cable
Reference
H07RN-F
Min. cable section
3G6 3G6 5G2.5 3G6 5G2.5
Max diameter
[mm]
18 18 17 18 17
Recommended cable
section
3G6 3G6 5G4 3G6 5G4
Max. diameter
[mm]
18 18 19.9 18 19.9
Wiring signal EDF, AFR, PV
mm
2
H05RN-F 2 x 0.75 mm
2
MODBUS cable
mm
2
H05RN-F 3 x 0.75 mm
2
Note: To avoid interference problems in the connection between the MODBUS cable from the internal unit to the external unit, use a shielded cable.

Table of Contents

Related product manuals