75 / GB
MENU
SUB-MENU
PARAMETER
DESCRIPTION
RANGE DEFAULT
0 NETWORK
0 2 BUS network
0 2 0 Network presence
System interface
Energy Manager
Heat Pump
Room Sensor
Zone Manager
0 3 System interface
030Zone number
No zone selected
Zone selected
1
031Room temperature correction - 3; +3 0
0 3 2 SW Version Interface
4 ZONE1 PARAMETERS
4 0 Setpoint
400T Day 10 - 30 °C 19°C Heat - 24°C Cool
401T Night 10 - 30 °C 16°C
402T set Z1 par. 4.2.5 - 4.2.6 20°C (LT) - 40°C (HT)
403Zone frost temperature 2 - 15 °C 5°C
4 1 Free parameters
4 2 Z1 Settings
420Zone 1 temperature range
Low Temp
High Temp
Low Temp
421Thermoregulation
Fix Flow T
Basic Thermoreg
Room T Only
Outdoor T Only
Room+Outdoor T
Basic Thermoreg
4 2 2 Slope 0,2 - 1 (LT); 1 - 3,5 (HT) 0,6 (LT) - 1,5 (HT)
423O set -14 ÷ +14 (HT); -7 ÷ +7 (LT) 0°C
424Room In uence Proportional 0 - 20°C 2°C (LT) - 10°C (HT)
425Max T 20°C ÷ 45°C (LT); 20°C ÷ 70°C (HT) 45°C (LT) - 60°C (HT)
426Min T 20°C ÷ 45°C (LT); 20°C ÷ 70°C (HT) 20°C (LT) - 20°C (HT)
4 3 Z1 Diagnostics
430Room T only read
431Room T setpoint only read
432Flow temperature only read
433Return temperature only read
4 3 4 Heat Request Z1 OFF - ON only read
435Pump Status OFF - ON only read
4 4 Z1 Zone Module Settings
440Zone pump modulation
Fixed
Modulating on DeltaT
Modulating on Pressure
Modulating on DeltaT
441Target deltaT for pump modulation 4 ÷ 25°C 7°C (LT) - 20°C (HT)
442Pump  xed speed 20 ÷ 100% 100%
4 5 Cooling
450T Set Cool Z1 par. 4.5.6 - 4.5.7
7°C [FC] - 18°C [UFH]
451Zone 1 Cooling Temp Range
Fan Coil
UFH
Fan Coil
452Thermoregulation type
ON/OFF
Fix Flow T
Outdoor T Only
ON/OFF
4 5 3 Slope [18;33] FC; [0-30] UFH
25 FC; 10 UFH
454O set [-2,5°C; +2,5°C]
0
456Max T
MinT -12°C [FC];
MinT - 23°C [UFH]
12°C [FC];
23°C [UFH]
457Min T 7°C-MaxT [FC]; 18-MaxT [UFH]
7°C [FC];
18°C [UFH
458Target deltaT for pump modulation cooling [-5; -20°C]
-5°C