Appendix A: Configuration presets
1X-F Series Installation Manual 91
EN 54-2 Evacuation
Table 47: Configuration presets
Preset Control panel EOL type Output type Sounder
outputs
Zone type
05 Two-zone Passive Class B 2 Mixed
05 Four-zone,
eight-zone
Passive Class B 4 Mixed
06 Two-zone Passive,
CleanMe
enabled
Class B 2 Mixed
06 Four-zone,
eight-zone
Passive,
CleanMe
enabled
Class B 4 Mixed
05 Two-zone EN 54-13
supervision
Class A 1 Odd: Automatic
Even: Manual
05 Four-zone,
eight-zone
EN 54-13
supervision
Class A 2 Odd: Automatic
Even: Manual
Table 48: Additional configuration characteristics
Default sounder delay
0
Default zone delay
0n
Start/Restart sounders
Start sounders or restart stopped sounders at user level
2 with fire alarm event
Table 49: Inputs and outputs
Input/Output
Standard EN 54-13
INPUT1
Remote reset Remote reset
INPUT2
Delays off Delays off
OUT1
Sounder circuit
Sounder circuit
OUT2
Sounder circuit
OUT3
Sounder circuit
Sounder circuit
OUT4
Sounder circuit
Note: Two
-zone control panels have only two outputs with EN 54-13 disabled (OUT1 and OUT2)
or a single output with EN 54-13 enabled (OUT1/2).