© 2020 Carrier. 1 / 16 P/N MAINST-ATS1170 (ML) • REV E • ISS 14DEC20
ATS1170 One-Door RAS Installation Sheet
EN
DA
DE
ES
FI
FR
IT
NL
NO
PL
PT
SV
EN: Installation Sheet
Mounting
ATS1170 PCB can be mounted in any existing control panel
housing which supports the size B board.
RAS DIP switch settings
See Figure, item 1.
Addressing : DIP switches 1 to 4 are used to identify the RAS
number. See also the ATS control panel installation guide.
DIP switches
See Figure, item 2.
T
ON: The unit is the last physical device on the databus (Term).
OFF: The unit is not the last physical device on the databus.
A
ON: Enable the offline programming mode.
OFF: Disable offline programming. Use this setting for standard
operation.
B
ON: Enable Financial Institution Magnetic swipe cards.
OFF: Enable ATS format Magnetic swipe cards.
C
ON: Magnetic swipe card reader used.
OFF: Wiegand reader is used.
ATS databus connection (system or local)
and earthing
See Advisor control panel installation guide.
Connections J2 and J3
J2: PWR 12 VDC supply input, COMMS positive and negative
data connection of the databus.
J3: Unlock relay (NO/C/NC). This relay is energised for the
unlock period, i.e. when L1 or L2 is flashing. See the ATS
control panel programming guide regarding this arming
station’s output controller group (programming menu 3).
LEDs
RX: LED flashes to indicate polling data is being received on
the system databus from the ATS control panel. If the LED
does not flash the control panel is not operational or the
databus is faulty (usually cabling).
TX: LED flashes to indicate RAS is replying to polling from the
ATS control panel. If the RX LED flashes but the TX LED does
not, the RAS is not programmed to be polled in the control
panel or is addressed incorrectly.
For details see the ATS control panel installation guide.
Reader wiring J1
/E
(Request to Exit) Input connection for door RTE button.
Shorting RTE to 0V will activate Request to Exit. (i.e. Request
to Exit button requires normally open contacts).
+5V
Power supply connection to the reader (100 mA max. at 5 V
for 2 seconds and 75 mA constant).
+12V
Power supply connection to the reader (100 mA max. at 12 V
for 2 seconds and 75 mA constant).
Caution: The + (positive) wire is connected to + 5V or +12 V
depending on the type of reader used.
0V
Negative power supply connection to reader.
D0
Data connection to reader.
T A B C
J3
J2
/E +12 +5 0V D0 D1 L2 L1 BZ NO CNC
READER
RELAY
J1
Tx Rx
(1)
(2)