Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 16
Parameter Description Range Def. Note
59
AdA
Temperature Alarms delay and
unlock display delay after defrost
oF Function disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
1
60
AoA
Open Door Alarm Delay
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
3
61
oo1
OUT1 function
oF No function;
ot
Temperature control (compressor);
dF Defrost;
Fn Fans;
Au Auxiliary;
At/-t Silenceable alarm;
AL/-L Not silenceable Alarm;
An/-n Stored Alarm;
on ON when the instrument is ON;
HE Heating (Neutral zone control)
L1
Showcase light with ECO function (ON with SP, OFF with SPE);
L2 Interior light (OFF with door closed, lit with door open).
ot
62
oo2
OUT2 function Fn
63
oo3
OUT3 function L1
64
obu
Buzzer function mode
oF Function disabled;
1 Active for alarms only;
2 Active for key pressed only;
3 Active for alarms and key pressed.
3
65
oFo
Auxiliary output function
oF Function disabled;
1 Control output ot delayed;
2 Manual activation by key.
oF
66
otu
Time relative to auxiliary output
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
67
tUF
/ Key Function
oF No function;
1 Eco Mode direct selection
(+ turn OFF the showcase light, if configured);
2 Switch ON/Switch OFF (Stand-by) the controller.
1
68
tFb
/ Key Function
oF No function;
1 Enable key to control the light (L1 and Au with Fo = 2).
1
69
tLo
Keyboard lock function delay
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 30 (min).
oF
70
tEd
Set Point change procedure
0 Disabled;
1 Active Set Point Direct change between limits SH... SE;
2 Active Set Point Direct selection between SP1, SP2 and SP3
with and keys.
2
71
tPP
Password to Access Parameter set-up
oF Function disabled;
001 ÷ 999.
oF
72
tdu
Filter to suppress the display of increasing temperature
variations lower than 0.1°
oF Function disabled;
0.1 ÷ 20.0.
oF
73
tdd
Filter to suppress the display of decreasing temperature
variations lower than 0.1°
oF Function disabled;
0.1 ÷ 20.0.
oF
74
ULU
Low mains alarm
oF Function disabled;
9 ÷ 27 (V x 10).
oF
75
UHU
High Mains alarm
oF Function disabled;
9 ÷ 27 (V x 10).
oF
76
UUd
Mains alamrs delay
oF Function disabled;
-01 ÷ -59 (s) ÷ 01 ÷ 99 (min)
oF
77
UOU
Mains Voltage calibration -30 ÷ 30 V 0