8. Wiring
Important: The figures shown in the table are for information purpose only. They should be checked and selected
to comply with the local/national codes of regulations. This is also subject to the type of installation
and conductors used.
• All wires must be firmly connected
• All wires must not touch the refrigerant piping, compressor or any moving parts of the fan motor.
• The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire
clamps as shown in the figure.
• The power supply cord must be equivalent to H05RN-F (245IEC57) which is the minimum requirement.
Model A5LCX 10/15C/CR A5LCX 20/25C/CR
Power supply cable size (mm
2
)
1.5 2.5
Number of wire 3 3
Interconnection cable size (mm
2
)
1.5 2.5
Number of wire 3 3
Recommended time delay fuse (A) 15 20
Voltage range 220V-240V / 1 Ph / 50Hz +